Brand: GCAN
Model: GCAN-PLC-324/326-E/R
Feature:
1. Software: OpenPCS;
2.Support Ethernet, RS232/485, CAN Bus interface;
3.Support master/slave station of CANopen protocol;
4.Support Modbus RTU/TCP master/slave protocol;
5.Support 5 languages of IEC61131-3 standard;
6.Providing customized services (programming/logo/software……
GCAN-PLC-324/326 —— with CAN bus communication capability
Model | Characteristic |
Communication bus | |||||||
Power | PNP DI | PNP DO | Relay DO | AI | AO | HSCI |
HSPO |
||
GCAN-PLC-324-E | 24V DC | 14 | 10 | / | 2 | 2 | 3 | 2 | 1*CAN+1*Ethernet+2*RS485 |
GCAN-PLC-324-R | / | 10 | / | ||||||
GCAN-PLC-324AC-E | 220V AC | 10 | / | 2 | |||||
GCAN-PLC-324AC-R | / | 10 | / |
Model | Characteristic |
Communication bus | |||||||
Power | PNP DI | PNP DO | Relay DO | AI | AO | HSCI |
HSPO |
||
GCAN-PLC-326-E | 24V DC | 24 | 16 | / | 2 | 2 | 3 | 2 | 1*CAN+1*Ethernet+2*RS485 |
GCAN-PLC-326-R | / | 16 | / | ||||||
GCAN-PLC-326AC-E | 220V AC | 16 | / | 2 | |||||
GCAN-PLC-326AC-R | / | 16 | / |
IO detailed parameters in the table:
- HSCI: High-Speed Counting Input
- HSPO: High-Speed Pulse Output
- PNP digital input 24V DC
- PNP digital output 24V DC
- Relay output 24V DC/220V AC 5A
- AI 0~10V image bit width 16Bit (0~65535)
- AO 0~20mA image bit width 12Bit (0~4095)
- DC pulse input counting 12-24V (multiplexed with DI3, DI4, DI5)
- VCC power supply / DC PWM high-speed pulse output (multiplexed with DO0, DO1, maximum pulse output
out 50KHz)
3 kinds of interface
CAN, Ethernet, RS232/485, follow ISO 11898, support CANopen/ Modbus RTU/ Modbus TCP, can be used as master or slave
5 programming language
Support SFC (Sequential Function Chart), LD (Ladder Diagram), FBD (Function Block), ST (Structured Text), IL (Instruction List)
After-sales service
7 x 24 hours every week after-sales technical support with our professional engineers to solve problems
Fixed I/O
The number of IO meets the standard, which is convenient for management and maintenance, and the whole machine is robust
Free software
Support OpenPCS software, follow IEC 61131-3, software free with GCAN-PLC
No dedicated bootloader